The Use of SCS in Intelligent Buildings
Introduction
Intelligent Building Systems (IBS) is Lucent's extension (or subset) of the Structured Connectivity Solution (SCS)
to include Fire, Security, Lighting HVAC and Energy Management systems. In fact, IBS is continually being
developed to include as much of the building environment systems as possible. There is
a continuing debate whether the I should stand for Intelligent, or perhaps
Integrated, which probably describes more accurately what the IBS actually does, i.e.
provides a common platform for environmental systems to communicate.
This document aims to aid those who are already familiar with Lucents SCS, to extend
SCS design to include for building environment systems as well as the familiar
Data/Voice applications. In addition, the document will mainly address the connection
of Honeywell specific controls equipment to the IBS. It is imperative that a fully trained
SCS engineer (i.e. one who has completed both the Installation & Maintenance course
and the Design & Engineering course) work closely with the BMS/lighting/fire and security engineers
in order to both educate on the best use of the structured cabling, and also to be
educated on the requirements of specific equipment. Issues that need to be discussed
early are the density and spacing of points, bus length capabilities and power requirements.
Although the building structure itself may commonly have a life cycle of 60 years or more,
the data systems have life cycles of the order of 3 years. Digital voice and video systems
have life cycles of 5 - 7 years and Building Management Systems (BMS) 7 - 14 years.
Traditionally, as systems are upgraded, the proprietory cabling for each system is
ripped out and installed for the next system. Systems are often only guaranteed with
specific cable types. The advantage is evident for an open cabling system that can
remain in place for 20 years, still covered by an applications and parts warranty,
having seen up to six data system changes, three voice system changes and a couple of BMS
changes
An open cabling system has existed for years in the data/voice
world and gives the customer greater freedom to mix and match data systems
without feeling tied in to a specific system provider. The same thing is now beginning
to happen in the building systems world as more and more system manufacturers design
their systems to operate across open structured cabling infrastructures.
Although many technological barriers have been overcome in integrating these different
systems, local codes such as local fire regulations may prohibit the use of certain
types of UTP.
What IBS does not do is integrate these building systems on a software/front end
presentation level. This software level of integration is another stage in the
bringing together of these systems, even common standards such as the Echelon Bus
are not yet 'common' enough for different manufacturer's equipment to communicate
with one another. This is due to the fact that individual manufacturers tweak the chips which
implement the Echelon standards so preventing interoperability.
A parallel in the data world is 10BaseT ethernet devices from one manufacturer talking
to 10BaseT devices from another manufacturer.
So why use a SCS for building systems?
- It reduces the cost to install the cabling.
- One specialist cabling contractor can install all the cabling for all systems, leaving
the system specialists to concentrate on their systems, therefore less time for them on site.
- The time to install the actual cabling is less.
- Commissioning the systems is quicker as the cabling system has already been 100% tested
according to the high standards normal in the data world.
- Improves flexibility in adding, moving and changing environmental systems.
General IBS Design
IBS is effectively SCS for control systems and the design considerations are almost
identical to those of the standard SCS. The following sub-systems exist in IBS:
- Campus Backbone Sub-system.
- Riser Backbone Sub-system.
- Equipment Sub-system - The key here is to centralise the control devices as much as possible
in order to minimise the number of custom control panels that often have to be made.
- Horizontal Sub-system.
- Coverage Area Sub-system - This is used to describe the equivalent of the Work Area Sub-subsystem
and typically has a wider area to consider.
- Administration Sub-system - Cheaper jumper wire can be used for patching, since the data speeds are very low
and crosstalk is not a problem.
Coverage Area
The Coverage Area topology can be quite different from the
normal Work Area topology, in that, devices can be looped or chained according to the
particular system requirements. The Information Outlets (I/O) are typically mounted
in places such as walls, ceiling voids and pillars as well as floor voids.
Extended Coverage Area wiring is appropriate for devices that are designed to be connected
in a bus or loop topology. Rather than having individual outlets for each device, devices
can be chained together from one outlet, or looped together between outlets. In addition,
fault tolerant device wiring is required for immediate detection of an open cable in a loop
for instance.
The size of coverage area varies depending on the type of environment. Experience has shown that
the following are reasonable guidelines:
- Office Areas - 25 sq. m (7-9 i/os per area, 3 for HVAC, 4 for security, 2 for lighting etc.).
- Factory, parking areas - 46 sq. m (4 i/os per area).
- Hotel - 5 i/os per room (fire, security, hvac).
- Plant room - blocks of outlets concentrated near AHUs (12 to 24 i/os per AHU),or
associated MCC equipment. Honeywell's 'Remote I/O' product for the XL10 controller
allows I/Os to be located remote from the controller and locally to the plant. This way
less cable is needed as the Remote I/O device communicates to the XL10 via the bus.
This compares with a typical office area of 9 sq. m with 4 i/os per work location.
The precise density of outlets would need to be carefully considered and a balance struck between over-stocking
on outlets that are never used and under-stocking so that ceiling tiles have to come down and new
cable runs installed when extra security doors are installed, for example. In addition, control
devices may be required under the floor e.g. wet systems. When tendering, careful consideration
needs to be made of both the current and possible future requirements of the occupier with
regards to the environmental management. What you are aiming for is a cabling infrastructure
that minimises future disruption of additional cabling installation, and flexibility such that
the occupier can swap and change around devices, much as they can with data/voice equipment.
Remember that a number of devices can hang off one socket (see later), it is important to
work with the controls manufacturer to at least understand the communications topology
of their equipment. An example, is a customer who may make great use of perimeter heating
and automatically controlled blinds or window openers. In this instance, you will probably
find that increasing the density of outlets near the edge of a floorspace is wise, after all
this is what we have done for years in the data/voice environment.
There are five main types of device signals used in control systems:
- Analogue Input (AI) - typically a 4 to 20mA current loop signal used to provide information
from remote devices such as temperature sensors to controllers.
- Analogue Output (AO) - typically a 4 to 20mA signal supplied by the controller
to control a remote device such as a valve or damper actuator.
- Digital Input (DI) - this is normally a binary signal supplied by an open/close
contact on a differential pressure switch located across water flow pumps, for example.
- Digital Output (DO) - a digital pulse from the controller to signal on/off or open/close
to remote devices. Normally via interposed relays which then allow through or shut off
power to devices.
- Control Bus - between controllers and front end computers.
For circuits where a maximum circuit resistance is important, the following table
can be used as a guide.
Circuit Resistance (ohms) |
Cable run (m) |
10 |
53 |
20 |
106 |
30 |
160 |
40 |
213 |
50 |
266 |
60 |
320 |
70 |
373 |
80 |
426 |
90 |
480 |
100 |
533 |
This table is based on the fact that the cable is 1061 (or equivalent) which contains
solid core 24AWG wires, two of which are used across a device. The resistance of this cable
is 9.4 ohms per 100m. The distance in the table is the cable distance not the circuit
distance, the circuit distance being to the device and back!
The following table is useful when connecting devices that require significant current
and a minimum operating voltage (based on 24v primary supply voltage):
Circuit Current |
50% drop i.e. 12v at device |
25% drop i.e. 18v at device |
10% drop i.e. 21.6v at device |
5% drop i.e. 22.8v at device |
Current (mA) |
Max. distance (m) |
Max. distance (m) |
Max. distance (m) |
Max. distance (m) |
10 |
6401 |
3219 |
1288 |
643 |
20 |
3219 |
1609 |
643 |
322 |
30 |
2146 |
1073 |
429 |
215 |
40 |
1609 |
805 |
322 |
161 |
50 |
1286 |
643 |
258 |
129 |
60 |
1073 |
536 |
215 |
107 |
70 |
920 |
456 |
182 |
91 |
80 |
792 |
402 |
161 |
80 |
90 |
701 |
354 |
139 |
69 |
100 |
643 |
320 |
129 |
64 |
200 |
322 |
160 |
64 |
32 |
500 |
129 |
64 |
26 |
13 |
1000 |
64 |
32 |
13 |
6 |
Highlighted in the above tables is a 50ohm device which is typical of a BMS device. This unit is fine up to 258m on the
SCS.
The following formula can be used to give the maximum cable distance allowed:
Distance = [V x v] / [100 x I x r]
Where:
Distance = Max. cable distance (m).
V = Voltage of device (v).
v = volt drop (%).
I = Current (Amps).
r = resistance of cable per m (ohms), in the case of 1061C, this has the value 0.188.
Again, this cable distance is assuming a two-wire circuit.
For an example, you may wish to work out the maximum distance allowed for a 1061 cable running to a door
solenoid which has been selected to draw 375 mA, supplied by a power supply giving 24v and a maximum
voltage drop allowed of 10%. Using the above formula:
Distance (m) = [24 x 10] / [100 x 0.375 x 0.188] = 34m
Therefore, the cable run must not exceed 34m.
The design guidelines suggest that a maximum of one amp per conductor is allowed (although this will not
get you very far!). If there are a number of devices connected via one four pair cable then the following table
gives a guide for the maximum current allowed per cable:
No. of pairs |
Max. current in wire (A) |
Current (A) per pair |
Current (A) per cable |
Max. Fusing (A) |
1 |
1 |
2 |
2 |
1.5 |
2 |
0.825 |
1.65 |
3.3 |
1 |
3 |
0.55 |
1.1 |
3.3 |
0.75 |
4 |
0.4125 |
0.825 |
3.3 |
0.5 |
Doubling up of conductors is permissible, but only for non-Fire systems, and then only for
increasing the signal transmission distances NOT the power capacity of the cable. There
is always the possibility of a break in one of the conductors, therefore putting more load
on the remaining conductors.
For audio voltage, the cable limitation is 70V RMS and the current 1Amp RMS.
Traditionally, controls devices present screw terminals for the connecting wire. However, these
terminals are designed for 16-18 AWG cable and are not suitable for the smaller 24AWG 1061C
cable. Before connecting the 24AWG cable, you need to crimp pins or spade lugs to the
ends of the wires to give the screw terminals a more resilient connection. The more
forward thinking controls manufacturers are now providing 110 blocks or RJ45 sockets
as part of the end device. There is always the option of adding such connections yourself,
certainly at the controller end, where there is often a custom panel made which can
provide space for 110 blocks/RJ45 sockets within the design of the panel itself.
Horizontal Sub-system
The total cable distance allowed is 100m. This is made up of 80m (as opposed to 90m in
the data/voice environment) for the frame to outlet run, 14m for the flylead connection
from the outlet to the end device(s) and 6m for the patch cable.
Determination of which closets the controllers are located is dependent on the particular
device protocol or voltage drop distance limitations. Certain devices, such as the 50ohm
example above, may be fine across a couple of cross connects and the riser sub-system,
provided the distance does not exceed 258m.
When chaining devices (as in the above diagram) keep to 5 devices or less off a single i/o,
off a single pair. These 5 devices may be in the same Coverage Area or in adjacent Coverage Areas.
Devices may be chained off one pair, or you could use another pair to connect another device,
obviously, for a four pair cable you are limited to 4 chained devices when using this method.
There is no reason why you could not use 25 pair cables to satellite 110 frames for further
distribution.
Standard rules apply when running the UTP cables near power cables. This is important if UTP wiring
is being installed in plant rooms where alot of high-voltage switching is likely to be happening. Generally,
the UTP cable will need to be on tray and metal trunking within the plant room environment. There are
no problems in sharing the tray with other cables provided they are not medium or high power cables. An
example, is sharing runs with Fire cables.
Although different devices can share the same 4-pair cable, these devices have to be part of the same system.
Different systems (e.g. data and security) must use separate cables.
In Plant rooms, multi-socket boxes can be used to provide concentration points for Air Handling Units (AHU)
to connect to using double ended RJ45 cables. This then allows the installation of extra capacity from the
MCC panel to the area near the AHU. The occupier may wish to replace the controls after 7 years with newer
technology that may require more inputs/outputs. There may be (always will be, actually!) changes of requirements both during
installation and early occupation, and extra control may be required. Plugging extra sensors into localised
sockets is far easier than running extra cables around a live plant room!
A common requirement nowadays is for CCTV. CCTV uses a baseband signal (< 10MHz) and is more than capable
of running down Category 5 UTP. There is however, some caveats; one is that you need to examine carefully
the specification of the security system. Telemetry signals (for motor control of the camera) can either be sent
down the same pair as the video signal (in which case distances can be limited to less than 100m using the
baseband video baluns), or the telemetry signals could be sent down a separate pair (thereby allowing greater
distances across cross-connects, perhaps up to 250m).
Whether you are in a pre or post-tender situation, it is a good idea to provide a small test rig (e.g. a box
of 1061C, a 100 block and a bank of RJ45's correctly terminated) for any equipment manufacturer
to test their equipment. This is especially useful for testing how far buses can operate reliably, or
CCTV signals with/or without telemetry. Issues can then be resolved before installation, and design changes
can occur on paper and not on site!
Riser Sub-system
Sizing of the riser cables is based on the number of pairs being used between closets and the number of pairs
likely to be used by devices that are patched across a number of closets, e.g. a temperature sensor. Building
systems must be kept in separate binder groups from the data/voice systems and each other, i.e. BMS systems
need to be in a different binder group from Security systems.
In addition, video systems must
be kept in separate sheaths from everything else due to the sensitivity and high speeds of the video signals.
Administration Sub-system
At least one Telecommunications Closet (TC) is required for every 900m^2 of office space according to the EIA/TIA.
The following patching can be carried out at the frame for 'Supervised' devices that require an End of
Line Resistor for detection of disconnections. The devices are 'chained' together, either individually or on a
per socket level, or a chain of devices off one socket.
Unsupervised circuits can be bridged (multi-dropped or T-tapped). This can be done at the outlet end using a
367A Bridging Adapter that provides 8 x RJ45 jacks that have each wire bridged from the original outlet
across all the corresponding pins of the RJ45s. The bridging could also be carried out on the frame as
detailed in the following diagram:
Equipment Sub-system
The Equipment can be BMS controllers, lighting controllers, bus repeaters, security controllers, Graphic
Front End systems etc. Communication Bus distances can vary from 150m to 1200m depending on the manufacturer's
specifications, and often repeaters can be inserted within the bus circuit as it comes back to the frame and
goes out again (e.g. Echelon bus repeaters for the Honeywell XL10 product).
Spade lugs and pins may still be required to connect jumper wire from the equipment field to the controller cards,
although it may be prudent to design controller panels with IDC 110 blocks instead of DIN rails. This would require
a culture change with the panel manufacturers, however it would make site installation much less fiddly. Ideally,
controllers should have RJ45s, or at the very least 110 blocks on the chassis for ease of connection in the field.
Front End equipment often runs on Ethernet LANs so making the job of distributing management much easier
than in the past. The data/voice systems can distribute the management stations.
The following tables give ideas on the uses of the cable pairs:
BMS:
Wire |
W-Bl |
Bl |
W-O |
O |
W-G |
G |
W-Br |
Br |
RJ45 Pin |
5 |
4 |
1 |
2 |
3 |
6 |
7 |
8 |
Bus |
+S |
-S |
|
|
|
|
|
|
Analogue-In |
S |
G |
|
|
|
|
|
|
4-20mA |
+24 |
S |
|
|
|
|
|
|
Analogue-Out |
S |
G |
|
|
|
|
|
|
Power |
|
|
|
|
|
|
AC |
AC |
Digital-In |
S1 |
G1 |
S2 |
G2 |
|
|
|
|
Digital-Out |
S1 |
G1 |
S2 |
G2 |
|
|
|
|
Security and Access Control:
Wire |
W-Bl |
Bl |
W-O |
O |
W-G |
G |
W-Br |
Br |
RJ45 Pin |
5 |
4 |
1 |
2 |
3 |
6 |
7 |
8 |
Data 0 |
X |
|
|
|
|
|
|
|
Data 1 |
|
X |
|
|
|
|
|
|
LED |
|
|
X |
|
|
|
|
|
+Power |
|
|
|
|
|
|
X |
|
Ground |
|
|
|
|
|
|
|
X |
Door Strike Power |
|
|
|
|
X |
|
|
|
Door Strike Common |
|
|
|
|
|
X |
|
|
Honeywell Specific Requirements
The Peer bus is used by Excel+ controllers to communicate with one another. The C-Bus (Central Bus) is used
by Excel 500, EMC controllers and IRC Multicontrollers. These buses use RS485 on 2 wires at 9.6Kb/s. The IRC
controllers have a local Room bus (R-Bus) which uses a 3.5mA current loop on 25VAC (three wires; one for forward
current and two for the return) and is not suitable for structured cabling. The old S-Bus (System Bus) is used to
connect the old Excel Classic controllers and uses RS422 on 2 wires at 2.4Kb/s.
The S-Bus, C-Bus and Peer bus can be multidropped (T-tapped) and up to 29 devices can be supported on each of
S-Bus and C-Bus types and 22 devices on the Peer bus. Using the 24AWG UTP, the bus distances have a maximum of
600m (exception being the C-Bus if a CSS
is connected in which case the distance can be up to 800m). Up to two bus extenders can be used in each bus, each
one extending the bus by 800m. The CSS now comes on a PC mounted board rather than
the old method of an RS232 connection from CSS to PC, which could only run 15m on UTP.
If the S-bus/C-Bus is star wired, ie. multidropped at the frame, up to a maximum of 7 branches, then the maximum bus
distance drops to 300m, unless a CSS is being used, in which case 400m is allowed. The restriction is that
a maximum of 5 devices is allowed on each branch.
The following table shows bus loads and lengths for the Peer bus:
Max. bus length (m) |
Max. loads (devices) |
152 |
22 |
304 |
15 |
457 |
13 |
609 |
11 |
914 |
7 |
1219 |
6 |
In a star configuration then the rules are that no more than 20 devices are allowed with no more than 6
on each branch, and the trunk length must be less than 152m whilst the branch lengths must be between
152m and 762m. The End of Line resistor configuration consists of two 62 ohm resistors each one bridging
from each of the two wires to a common point. The EOLRs are attached at the extreme ends of the bus.
Generally, end sensor cable distances should be no more than 183m to minimise noise from outside sources.
How many devices, and how far cable runs can be, will depend on the individual manufacturers specifications.
The standard SCS guidelines such as 80m maximum horizontal runs, and so forth, provide a basis for designing
the generic structured cabling. It could be the case that some manufacturers will require to site certain
equipment at every closet in order to minimise distance problems (such is the case with LAN equipment). In other
cases, and particularly with lower data speeds, the equipment could be located more centrally such that some
devices are linked across a number of cross connects.
Current Fire codes prevent the use of the SCS cabling in Fire systems other than backup monitoring, even the
plenum rated cable is not sufficient. This may change in the next 5 years as consultants try to persuade
the Fire authorities of the benfits of SCS systems and alternative designs that get round having to use
mineral sheathed cables.
(The tables in this document were originally sourced from Avaya Technologies
and are based on their SCS Systimax Product).
|